GMI D5090S Safety relay SIL3 Relay Out Module for 5 A NE Loads

GMI D5090S Safety relay SIL3 Relay Out Module for 5 A NE Loads

Model: D5090S

Supplier: GMI

Categories: Safety Relay

After sales service. If you have any questions, click here.

PRODUCT DESCRIPTION

GMI D5090S Safety relay SIL3 Relay Out Module for 5 A NE Loads 



Description:

The D5090 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available two NO contacts for Normally Energized (NE) loads, in order to disconnect the load on both supply lines, and a NC contact for service purpose. A wide compatibility towards different DCS/PLC is guaranteed: driving pulse testing is permitted by a dedicated internal circuit, which prevents contact and LED flickering.


FEATURES

  • SIL 3 / SC 3 for NE loads with NE driver

  • Installation in Zone 2/Div. 2

  • Up to 5 A functional / 6 A inrush current

  • Load disconnection on both supply lines available

  • Compatible with DCS/PLC pulse testing

  • Service contact available

  • Input/Output isolation


Input

Type24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes.
Current Consumption45 mA @ 24 Vdc, typical.
Power Dissipation1.1 W @ 24 Vdc, typical.

Output

Type1 voltage free SPDT relay contact identified with outputs: Out 1 (NO contact) terminals 13-21 and Service Load Out (NC contact) terminals 13-15; 1 voltage free SPST relay contact identified with output Out 2 (NO contact) terminals 14-22. Terminals 13-21 (Out 1) and 14-22 (Out 2) are open when relay is de-energized, closed in energized relay condition. Service load output (not SIL) at terminals 13-15 is normally close when relay is de-energized, open in energized relay condition.
Contact materialAg Alloy (Cd free), gold plated.
Contact rating5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load).
Contact min. switching current1 mA.
Contact inrush current6 A @ 24 Vdc, 250 Vac.
DC and AC load breaking capacityrefer to Instruction Manual.
Mechanical / electrical life5 * 10⁶ / 3 * 10⁴ operation, typical.
Operate / release time55 / 30 ms, typical.

Isolation

Test VoltageInput / All Outs 2.5 kV; Out 1/Out 2 500V.

Environmental conditions

Operating temperaturetemperature limits -40 to +70 °C.
Storage temperaturetemperature limits -45 to +80 °C.

Mounting

TypeDIN-Rail 35 mm, or on custom Term. Board.
Weightabout 125 g.
Connectionby polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
DimensionsWidth 12.5 mm, Depth 123 mm, Height 120 mm.

...