GMI D5096S-100 Safety relay SIL3/2 5 A Relay with LFD & Universal Fault Mirror

GMI D5096S-100 Safety relay SIL3/2 5 A Relay with LFD & Universal Fault Mirror

Model: D5096S-100

Supplier: GMI

Categories: Safety Relay

After sales service. If you have any questions, click here.

PRODUCT DESCRIPTION

GMI D5096S-100 Safety relay SIL3/2 5 A Relay with LFD & Universal Fault Mirror


Description:

The D5096-100 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available 2+2 NO relay contacts connected in parallel and then in series to avoid spurious trip and to increase process availability. High process availability SIL 3 Safety Function for Normally Energized (NE) and SIL 2 for Normally De-energized (ND) / F&G loads is available. Load can be isolated from supply on both polarities. A wide compatibility towards different DCS/PLC is guaranteed: driving pulse testing is permitted by a dedicated internal circuit, which prevents contact and LED flickering. Line and load short/open circuit detection and load voltage monitoring are provided, both when the load is off and when the load is on. The fault in the field is directly mirrored to the PLC DO by opening the input and it is also reported by opening the fault output. The fault mirroring technique guarantees a wide compatibility to PLC DO cards.



FEATURES:

  1. SIL 3 / SC 3 for NE loads with NE driver

  2. SIL 2 / SC 3 for ND loads with ND driver

  3. Installation in Zone 2

  4. Up to 5 A functional / 6 A inrush current

  5. Load disconnection on both supply lines available

  6. High process availability to avoid spurious trips

  7. Compatible with DCS/PLC pulse testing

  8. Line & Load short/open circuit detection

  9. Load voltage monitoring

  10. Universal field fault mirroring to the PLC DO

  11. Service contact available

  12. Input/Output/Supply isolation


Supply

Type24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption15 mA @ 24 Vdc, typical.
Power Dissipation0.35 W @ 24 Vdc, typical.

Input

Type24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes.
Current Consumption45 mA @ 24 Vdc, typical.
Power Dissipation1.1 W @ 24 Vdc, typical.

Output

TypeVoltage free 2+2 SPST relay contact (2 paralleled contacts in series) at terminals 7-11 and 8-12, close when relay energized, open in de-energized condition.
Contact materialAg Alloy (Cd free), gold plated.
Contact rating5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load).
Contact min. switching current1 mA.
Contact inrush current6 A @ 24 Vdc, 250 Vac.
DC and AC load breaking capacityrefer to Instruction Manual.
Contact current deratingrefer to Instruction Manual.
Mechanical / electrical life:5 * 10⁶ / 3 * 10⁴ operation, typical.
Operate / release time30 ms / 30 ms, typical.

Isolation

Test VoltageOut/In 1.5 kV; Out/Supply 1.5 kV; Out/Fault Out 1.5 kV; In/Supply 500 V; In/Fault Out 500 V; Supply/Fault Out 500 V.

Environmental conditions

Operating temperaturetemperature limits –40 to +70 °C.
Storage temperaturetemperature limits -45 to +80 °C.

Mounting

TypeDIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weightabout 125 g.
Connectionby polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
DimensionsWidth 12.5 mm, Depth 123 mm, Height 120 mm.

...