GMI D5098S Safety relay SIL3 Relay Out Module for 5 A NE Loads
Description:
The D5095 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available 2+2 NC relay contacts connected in parallel and then in series to avoid spurious trip and to increase process availability. High process availability SIL 3 Safety Function for both Normally Energized (NE) and Normally De-energized (ND) / F&G loads is available. Load can be isolated from supply on both polarities. A wide compatibility towards different DCS/PLC is guaranteed: driving pulse testing is permitted by a dedicated internal circuit, which prevents contact and LED flickering.
FEATURES:
SIL 3 / SC 3 for NE loads with NE driver
Installation in Zone 2
Up to 5 A functional / 6 A inrush current
Compatible with DCS/PLC pulse testing
Service contact available
Input/Output isolation
Input
| Type | 24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes. |
| Current Consumption | 45 mA @ 24 Vdc, typical |
| Power Dissipation | 1.1 W (D5098D), @ 24 Vdc, typical. |
Output
| Type | 1 voltage free SPDT relay contact identified with outputs: Out 1 (NO contact) terminals 7-8 and Service Load Out 1 (NC contact) terminals 7-11; 1 voltage free SPDT relay contact identified with outputs Out 2 (NO contact) terminals 9-10 and Service Load Out 2 (NC contact) terminals 9-12 (only for D5098D). Terminals 7-8 (Out 1) and 9-10 (Out 2, only for D5098D) are open when relay is de-energized, closed in energized relay condition. Service load outputs (not SIL) at terminals 7-11 and 9-12 (only for D5098D) are normally closed when relay is de-energized, open in energized relay condition. |
| Contact material | Ag Alloy (Cd free), gold plated. |
| Contact rating | 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). |
| Contact min. switching current | 1 mA. |
| Contact inrush current | 6 A @ 24 Vdc, 250 Vac. |
| DC and AC load breaking capacity | refer to Instruction Manual. |
| Contact current derating | refer to Instruction Manual. |
| Mechanical / electrical life | 5 * 10⁶ / 3 * 10⁴ operation, typical. |
| Operate / release time | 30 ms / 20 ms, typical. |
Isolation
| Test Voltage | Output/Input 1.5 kV; Input/Input 500 V; Output/Output 1.5 kV. |
Environmental conditions
| Operating temperature | temperature limits –40 to +70 °C. |
| Storage temperature | temperature limits -45 to +80 °C. |
Mounting
| Type | DIN-Rail 35 mm, or on custom Term. Board. |
| Weight | about 110 g |
| Connection | by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |
...