GMI D5099S Safety relay Relay Out Module for 5 A Loads
Description:
The D5099 is a relay module, which makes available a SPDT (Single Pole Double Throw) contact isolated from the input. Compatibility with specific DO cards with pulse testing needs to be verified.
FEATURES:
Installation in Zone 2/Div. 2
Up to 5 A functional / 6 A inrush current
Both NO and NC contact available
Low activation coil current (< 10 mA)
Input/Output isolation
Input
| Type | 24 Vdc nom (21.6 to 27.6 Vdc). Relay coils are internally protected with suppressor diodes. |
| Current Consumption | 10 mA @ 24 Vdc, typical. |
| Power Dissipation | 0.24 W @ 24 Vdc, typical. |
Output
| Type | A voltage-free SPDT relay contact: NO contact at terminals 7-8 and NC contact at terminals 9-10. Terminals 7-8 (NO contact) are open when relay is de-energized, closed in energized relay condition. Terminals 9-10 (NC contact) are closed when relay is de-energized, open in energized relay condition. |
| Contact material | Ag Alloy (Cd free), gold plated. |
| Contact rating | 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). |
| Contact min. switching current | 1 mA. |
| Contact inrush current | 6 A @ 24 Vdc, 250 Vac. |
| DC and AC load breaking capacity | refer to Instruction Manual. |
| Mechanical / electrical life | 5 * 10⁶ / 3 * 10⁴ operation, typical. |
| Operate / release time | 6 ms / 12 ms, including contact bounce time, typical. |
Isolation
| Test Voltage | Output/Input 1.5 kV. |
Environmental conditions
| Operating temperature | temperature limits –40 to +70 °C. |
| Storage temperature | temperature limits -45 to +80 °C. |
Mounting
| Type | On custom Term. Board. |
| Weight | about 100 g. |
| Connection | by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |
...
For more inquiry,please contact me freely,
Contact: Jellery Xu
+86 15071090630(Whatsapp&Wechat)
Email: jellery@hkxytech.com & jellery@whxyauto.com