GMI D5290S-079 Safety relay SIL3 115 Vac Relay Out Module for 5 A NE/ND Loads

GMI D5290S-079 Safety relay SIL3 115 Vac Relay Out Module for 5 A NE/ND Loads

Model: D5290S-079

Supplier: GMI

Categories: Safety Relay

After sales service. If you have any questions, click here.

PRODUCT DESCRIPTION

GMI D5290-079 Safety relay SIL3 115 Vac Relay Out Module for 5 A NE/ND Loads



Description:

The D5290-079 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available up to four NO contacts and two NC contacts, which can be externally connected for multiple Normally Energized (NE) or Normally De-energized (ND) loads, with single or both supply lines disconnection, and additional service loads. Compatibility with specific DO cards with pulse testing needs to be verified. This relay module is not suitable for low-current consumption applications (system-to-system signalling, driving LEDs, etc.).


FEATURES:

  • SIL 3 / SC 3 for NE/ND loads with NE driver

  • Up to 5 A functional / 8 A inrush current

  • Load disconnection on both supply lines available

  • Service contact available

  • Multiple contacts (up to 4 NE or 2 ND loads)

  • Input/Output isolation


Input

Type115 Vac nom (95 to 130 Vac).
Current Consumption25 mA @ 115 Vac, typical.
Power Dissipation2.5 W @ 115 Vac, typical.

Output

Type2 voltage free SPDT (= NO contact + parallel of 2 NC contacts) relay contacts identified with outputs: Out S_1 & Out P_1 and Out S_3 & Out P_2; 2 voltage free SPST (NO) relay contacts identified with: Out S_2 and Out S_4. Terminals 13-14 (Out S_1), 15-16 (Out S_2), 21-22 (Out S_4) and 23-24 (Out S_3) are: open when relay is de-energized, closed in energized relay condition. Terminals 17-18 (Out P_1) and 19-20 (Out P_2) are: closed when relay is de-energized, open in energized relay condition.
Contact materialAg Alloy (Cd free).
Contact rating 5A 250 Vac 1250 VA, 5 A 250 Vdc 175 W (resistive load).
Contact inrush current8 A @ 30 Vdc, 250 Vac.
Contact min. switching current100 mA.
DC and AC load breaking capacityrefer to Instruction Manual.
Mechanical / electrical life10 * 10⁶ / 5 * 10⁴ operation, typical.
Operate / release time12 ms / 4 ms, typical.

Isolation

Test VoltageInput/All Outs 2.5 kV; Out S_1 & Out P_1/Out S_3 & Out P_2, Out S_2, Out S_4 500 V; Out S_3 & Out P_2/Out S_2, Out S_4 500 V; Out S_2/Out S_4 500 V.

Environmental conditions

Operating temperaturetemperature limits -40 to +60 °C.
Storage temperaturetemperature limits -45 to +80 °C.

Mounting

TypeDIN-Rail 35 mm.
Weightabout 170 g.
Connectionby polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).