GMI D5290S-091 Safety relay SIL3 230 Vac Relay Out Module for 10 A NE Loads

GMI D5290S-091 Safety relay SIL3 230 Vac Relay Out Module for 10 A NE Loads

Model: D5290S-091

Supplier: GMI

Categories: Safety Relay

After sales service. If you have any questions, click here.

PRODUCT DESCRIPTION

GMI D5290S-091 Safety relay SIL3 230 Vac Relay Out Module for 10 A NE Loads


Description:

The D5290-091 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available two NO contacts for Normally Energized (NE) loads, in order to disconnect the load on both supply lines, and a NC contact for service purpose. Compatibility with specific DO cards with pulse testing needs to be verified. This relay module is not suitable for low-current consumption applications (system-to-system signalling, driving LEDs, etc.).


FEATURES:


  • SIL 3 / SC 3 for NE loads with NE driver

  • Up to 10 A functional / 16 A inrush current

  • Load disconnection on both supply lines available

  • Service contact available

  • Input/Output isolation

  • Input/Output isolation


Input

Type230 Vac nom. (195 to 250 Vac).
Current Consumption10 mA @ 230 Vac, typical.
Power Dissipation2 W @ 230 Vac, typical.

Output

Type1 voltage free SPDT relay contact identified with outputs: Out 1 (NO contact) terminals 13-21 and Service Load Out (NC contact) terminals 13-15; 1 voltage free SPST relay contact identified with output Out 2 (NO contact) terminals 14-22. Terminals 13-21 (Out 1) and 14-22 (Out 2) are open when relay is de-energized, closed in energized relay condition. Service load output (not SIL) at terminals 13-15 is normally close when relay is de-energized, open in energized relay condition. 
Contact materialAg Alloy (Cd free). 
Contact rating10 A 250 Vac 2500 VA, 10 A 250 Vdc 300 W (resistive load).
Contact inrush current16 A @ 24 Vdc, 250 Vac.
Contact min. switching current100 mA.
DC and AC load breaking capacityrefer to Instruction Manual.
Mechanical / electrical life5 * 10⁶ / 5 * 10⁴ operation, typical. 
Operate / release time8 ms / 4 ms, typical.

Isolation

Test VoltageInput/All Outs 2.5 kV; Out 1/Out 2 500 V.

Environmental conditions

Operating temperaturetemperature limits -40 to +60 °C.
Storage temperaturetemperature limits -45 to +80 °C.

Mounting

TypeDIN-Rail 35 mm.
Weightabout 165 g.
Connectionby polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
DimensionsWidth 22.5 mm, Depth 123 mm, Height 120 mm.

...




For more inquiry,please contact me freely,